Building Safety Act 2022: What Is It and Who Must Comply?

The Building Safety Act 2022 is the law that rebuilt building safety regulation in England after the Grenfell Tower fire. It received Royal Assent on 28 April 2022. The Act created the Building Safety Regulator and a stricter regime for higher-risk buildings, from design to occupation. It also made competence a legal duty for all building and design work in England and protects leaseholders from the cost of historical safety defects.

What it actually says

The test for an occupied higher-risk building: “a building in England that (a) is at least 18 metres in height or has at least 7 storeys, and (b) contains at least 2 residential units”

Section 65(1), Building Safety Act 2022, on legislation.gov.ukDuring design and construction the test is wider: hospitals and care homes of that height count too.
Act of ParliamentApplies to: Clients, designers and contractors on building work in England, and the accountable persons for occupied higher-risk buildings.

Key points

Training that covers this law

What is the Building Safety Act 2022?

The Building Safety Act 2022 (2022 c. 30) is an Act of Parliament. Section 1 sets its aim: to secure the safety of people in and around buildings and to improve the standard of buildings.

It received Royal Assent on 28 April 2022 and came into force in stages. A few parts, such as the new homes ombudsman scheme, are still not in force. The Act extends to England and Wales, and a few parts cover the whole UK. Its duties for occupied higher-risk buildings apply in England only. Its building control changes, including a Welsh higher-risk building regime and the duty holder rules, came into force in Wales on 1 July 2026.

Four changes sit at its heart. First, it set up a new regulator. It also created a regime for higher-risk buildings that runs from planning to occupation. Then came duty holder and competence rules for all building work, and finally protection for leaseholders from the cost of fixing historical defects.

What is a higher-risk building?

Once people live in it, a building in England is higher-risk if it meets two tests (section 65). It is at least 18 metres tall or has at least 7 storeys. It also contains at least 2 homes. The height test says or, so a 7 storey block under 18 metres still counts.

However, the definition is wider during design and construction. Hospitals and care homes of that height count too (section 120D of the Building Act 1984 and SI 2023/275). A building that is entirely a hospital or care home drops out of the regime once it is occupied.

In December 2025 the regulator reviewed the definition and found “insufficient evidence” to change it, so the test above still applies.

Who is the Building Safety Regulator?

The Building Safety Regulator enforces the Act. It began in 2021 inside the Health and Safety Executive. On 1 October 2023 it became the building control authority for higher-risk buildings in England.

Since 27 January 2026 it has stood alone. It is now an executive non-departmental public body, sponsored by the Ministry of Housing, Communities and Local Government (SI 2026/20). Many guides still call it part of HSE, which is out of date. The move left its functions unchanged. It also replaced HSE as the statutory consultee on planning applications for high-rise homes.

Looking ahead, the government plans a single construction regulator built on the same foundation, with implementation expected to start from 2028, once Parliament passes the new law.

The three gateways for higher-risk buildings

“Gateway” is the official name for three hold points that every higher-risk building project in England has to pass. The word is not in the Building Safety Act itself. Instead, gateway one comes from planning law, and gateways two and three from the Building (Higher-Risk Buildings Procedures) (England) Regulations 2023.

GatewayWhat the law requiresIn practice
Gateway 1Planning
A planning application for a building of 18 metres or 7 storeys or more, with two or more homes or educational accommodation, has to include a fire statement (article 9A of the Development Management Procedure Order 2015). The Building Safety Regulator is a statutory consultee (Schedule 4 to the same Order).
Fire safety shapes the layout, access and water supply from the first drawing.
Gateway 2Building control approval
The client must apply for, and be granted, the regulator’s building control approval before higher-risk building work starts (regulation 3, SI 2023/909). The regulator decides a valid application for a new building within 12 weeks, unless both sides agree longer.
No approval, no start. Building work without it is a criminal offence.
Gateway 3Completion certificate
A home in the building cannot be occupied before the regulator issues a completion certificate (section 76). The regulator decides within 8 weeks. Where the Building Safety Levy applies, it also needs the local authority’s confirmation that the levy is settled.
Plan the handover early: registering the building needs the certificate.

Accountable persons and their duties

Once people live in a higher-risk building, the Building Safety Act puts the duties on its accountable persons. An accountable person owns, or has a repairing obligation for, part of the common parts, such as the structure and exterior (section 72). Where there are several, the principal accountable person is the one responsible for the structure and exterior (section 73).

Government guidance is clear: accountable persons cannot hand their legal duties to someone else. Others can help, but the duty stays with them. As a result, the people who own and repair a building need to understand the duties below themselves.

Registering the building and managing its risks

SectionWhat it requiresIn practice
77 and 78Register the building
The principal accountable person must register an occupied higher-risk building with the regulator. Occupation without registration is an offence.
Register before the first residents move in.
79Building assessment certificate
When the regulator directs it, the principal accountable person applies for a certificate within 28 days.
Keep the safety case report ready for that call.
83Assess building safety risks
Each accountable person assesses the risk of fire spreading and of structural failure, as soon as reasonably practicable.
Start with the two risks the Act names: fire spread and structural failure.
84Manage building safety risks
Each accountable person takes all reasonable steps to stop a building safety risk happening and to reduce how serious it would be.
Turn the assessment into actions, each with an owner and a date.
85 and 86Safety case report
The principal accountable person prepares a safety case report and tells the regulator it exists, as soon as reasonably practicable.
The regulator says these duties have been enforceable since January 2024.

Reporting, records and residents

SectionWhat it requiresIn practice
87Mandatory occurrence reporting
The principal accountable person runs a reporting system, and each accountable person reports safety occurrences. A notice goes in as soon as reasonably practicable, and a report within 10 days.
Make sure staff know what counts as a safety occurrence.
88Keep the golden thread
Each accountable person keeps the prescribed building information, electronically and up to date.
One digital record per building, kept current.
91Residents’ engagement strategy
The principal accountable person prepares a strategy for involving residents in building safety decisions.
Residents get a copy, and their views feed into decisions.
93Complaints procedure
The principal accountable person runs a procedure for residents’ building safety complaints.
Log each complaint, the response and the outcome.

What is the golden thread?

The golden thread is the digital record of a higher-risk building’s information. Although it is central to the Building Safety Act regime, the phrase is not in the Act. Regulations define it, for design and construction in regulation 31 of SI 2023/909, and for occupied buildings in section 88 with SI 2024/41.

Duty holders and competence for all building work

Many guides miss this part. Through the Building Safety Act, Part 2A of the Building Regulations 2010 sets duties for every building and design project in England. They have applied since 1 October 2023, whatever the height of the building. Wales followed on 1 July 2026.

The competence rule

Regulation 11F sets the competence rule. Anyone carrying out building or design work must have “the skills, knowledge, experience and behaviours necessary”, or organisational capability for a business. Regulation 11Q lists those behaviours, including refusing work that would not comply and refusing work beyond your own skills. Anyone who stops meeting the rule must tell whoever appointed them (regulation 11I).

For example, domestic clients pass most of their client duties to the contractor or designer, and minor work listed in Schedule 4 is exempt for clients. A CDM principal designer or principal contractor can also take the same role under the Building Regulations. The competence rules for each role differ, though.

Does the Building Safety Act require training?

No regulation in this regime names a training course. The legal test is competence. Individuals need the skills, knowledge, experience and behaviours for their role, under regulation 11F for building work and SI 2023/907 for accountable persons.

Government guidance lists formal training as one way to show that competence, alongside a portfolio of relevant work. Trainees can do the work while they learn, as long as a competent person supervises them. In addition, contractors and accountable persons must give their people the right instructions and information.

Building Safety Act Training from ProCompliance covers the regime for higher-risk buildings: duty holders, the accountable person, the golden thread and how to involve residents. It runs online in approx. 60 minutes, is CPD accredited and gives each learner a certificate. Teams can take it in our LMS, The Globe, or as SCORM 1.2 or 2004 in their own LMS, in 50 languages.

Courses that cover the Building Safety Act 2022

This ProCompliance course names the Building Safety Act 2022 as its governing framework. Its page states its accreditation, running time and certificate.

See also: Training for construction teams.

Protections for leaseholders

If you hold a qualifying lease in a relevant building, you pay nothing to fix unsafe cladding (Schedule 8). A relevant building is in England and has at least two homes. It is also at least 11 metres high or has at least 5 storeys (section 117). A qualifying lease is a long lease of a single flat, granted before 14 February 2022, where the leaseholder pays a service charge and, on that date, the flat was their main home or they owned no more than three homes in the UK in total (section 119).

For other historical safety defects, Schedule 8 caps what a qualifying leaseholder pays at £10,000, or £15,000 in Greater London. Higher caps apply to leases worth over £1 million.

The Building Safety Act also extended the time limit for claims under the Defective Premises Act 1972. Claims for past work now have 30 years, and claims arising from now on have 15 years (section 135).

Offences and penalties

The serious offences under the Building Safety Act carry up to two years in prison, a fine, or both, on conviction in the Crown Court. Some add a daily fine while the breach continues. They include:

Because of section 161 of the Act and section 112A of the Building Act 1984, directors and managers can also be prosecuted personally where an offence happens with their consent or connivance, or through their neglect.

The Building Safety Act and the Fire Safety Order

Section 156 of the Act changed the Regulatory Reform (Fire Safety) Order 2005, from 1 October 2023. The responsible person under the Order now has more to do in every building it covers, as well as in higher-risk ones.

Section 156 would also add a competence test for anyone helping with a fire risk assessment. That part is not yet in force.

Building Safety Act terms explained

What changed in 2025 and 2026

Official sources

Common questions

Is the Building Safety Regulator part of HSE?

Not any more. The regulator started inside HSE. Since 27 January 2026 it has been a standalone public body, sponsored by the Ministry of Housing, Communities and Local Government. Its functions did not change with the move.

Does the Building Safety Act apply in Wales?

Partly. The Act extends to England and Wales. Its building control changes took effect in Wales on 1 July 2026, with a wider Welsh higher-risk definition that counts buildings with one residential unit and includes children’s homes. Its duties for occupied buildings apply in England only, and Wales covers those through its own Building Safety (Wales) Act 2026, which comes into force in stages.

Are care homes and hospitals higher-risk buildings?

During design and construction, yes, once they reach 18 metres or 7 storeys. A building that is entirely a care home or hospital falls outside the regime for occupied buildings.

Who is the accountable person for a building?

Whoever owns the common parts, such as the structure and exterior, or has a repairing obligation for them. Where there are several, the one responsible for the structure and exterior is the principal accountable person. Neither can hand the legal duties to someone else.

Does the Act require a building safety manager?

No. The term does not appear in the Act. The duties sit with the accountable persons, who can get help from others while keeping the legal responsibility.

Is Building Safety Act training a legal requirement?

The law asks for competence, not a named course. Anyone doing building or design work must have the skills, knowledge, experience and behaviours the work needs. Government guidance lists formal training as one way to show that competence.

When did the Building Safety Act come into force?

In stages. Royal Assent came on 28 April 2022, and the leaseholder protections began on 28 June 2022. On 1 October 2023 the regulator became the building control authority for higher-risk buildings and the competence rules began. Most duties for occupied buildings followed on 16 January 2024.

Does the Building Safety Act apply to all building work?

Part of it does. The duty holder and competence rules in Part 2A of the Building Regulations 2010 apply to building and design work across England, whatever the building. The gateways, registration and accountable person duties apply only to higher-risk buildings.

Is my building over 11 metres covered by the Building Safety Act?

For leaseholder protection, usually: self-contained buildings in England of 11 metres or 5 storeys with at least two homes are relevant buildings, unless they are leaseholder-owned or commonhold. The higher-risk building regime starts higher, at 18 metres or 7 storeys.

Who is liable under the Building Safety Act?

Clients, designers and contractors answer for building work, and accountable persons answer for occupied higher-risk buildings. Directors and managers can also be liable where an offence happens with their consent or connivance, or through their neglect.

What is the Building Safety Levy?

A tax on new residential developments in England, in force since 1 October 2026. It applies to developments of 10 or more new homes, or 30 or more bedspaces of purpose-built student housing.

This plain English summary is not legal advice. The facts above were checked against the official text. This page links to that text, and you should rely on it instead. Some duties depend on your own risk assessment, so only that assessment can tell you what they mean.

Meeting this duty

Training that answers what the Building Safety Act 2022 asks

Reading the duty is the easy part. The Globe maps courses to the law they cover. It then records each completion for you. As a result, the evidence exists before an inspector asks for it.

5.0 from 75 reviews on Reviews.io
Join 1,000+ UK organisationstraining with us
Most courses are accredited IOSH, CPD or IATP, shown per course
Real UK support01344 957 700, weekdays